4.9. Status Indications
The following table lists the Piccolo amplifier status indications.
Function Latch
Option
AOK SO1 SO2 SO3
1 Amplifier OK
(AOK)
N/A Low Open collector Open collector Open collector
2 External disable No Low Low Open collector Low
3 Current limit No Low Open collector Open collector Low
4 Short Yes Open collector Low Open collector Low
5 Over
temperature
Yes Open collector Open collector Low Low
6 Internal supplies
protection
No Open collector Low Low Open collector
7 Under voltage No Open collector Low Open collector Open collector
8 Over voltage No Open collector Open collector Low Open collector
9 Shunt* No Low Open collector Low Open collector
10 Power up reset No Open collector Open collector Open collector Open collector
11 Commutation
failure
Yes Open collector Low Low Low
* This indication can be used as a digital input for activating an external shunt regulator.
Table 9: Piccolo Status Indications
Notes:
• Without latch mode:
The status indications are reset when the fault disappears.
• With latch mode:
The Short, Over Temperature and Commutation Failure status indications are reset when
the enable signal is temporarily removed from the enable input.
• Multiple faults:
Only the reading of the first fault is reliable. Additional faults add on to the status outputs
and the indication is therefore meaningless.